3.8.6 How to install a cable probe in the tank
• Use two persons to lift the housing and the probe above the process connection.
• Hold the device 1 m / 3½ ft above the tank.
• Unwind the probe carefully into the tank.
Figure 3-35: Wind cable probes and electrical cables carefully
1 Do not wind cable probes less than 400 mm / 16¨ in diameter.
2 Do not wind the electrical cable less than 330 mm / 13¨ in diameter.
WARNING!
If you bend the probe too much, you will damage the device and it will not measure accurately.
Figure 3-36: Installation of devices with cable probes
1 >1 m / 3½ ft