Quickstart EN Owner's manual

INSTALLATION 2
13
OPTIFLEX 2200 C/F
www.krohne.com08/2013 - 4000622103 - QS OPTIFLEX 2200 R03 en
2.8 Installation recommendations for liquids
2.8.1 General requirements
Clearance between the probe and other objects in the tank
Figure 2-14: Installation recommendations for liquids
1 The electromagnetic (EM) field generated by the device. It has a radius of R
min
. Make sure that the EM field is clear of
objects and product flow. Refer to the table that follows.
2 If there are too many objects in the tank, install a bypass chamber or stilling well.
3 Keep the probe straight. If the probe is too long, shorten the probe length. Make sure that the device is configured with
the new probe length. For more data on the procedure, refer to the handbook.
4 Empty space. Refer to the table that follows.
Probe type Empty space (radius, R
min
), around the probe
[mm] [inches]
Coaxial 0 0
Double rod / cable 100 4
Single rod / cable 300 12