3 ELECTRICAL CONNECTIONS
40
OPTIFLEX 2200 C/F
www.krohne.com 08/2013 - 4000622103 - QS OPTIFLEX 2200 R03 en
3.5 Protection category
Make sure that the gaskets are not damaged.
Make sure that the electrical cables are not damaged.
Make sure that the electrical cables agree with the national electrical code.
The cables are in a loop in front of the device 1 so water does not go into the housing.
Tighten the cable feedthroughs 2.
Close unused cable feedthroughs with dummy plugs 3.
The diameter of the outer sheath of the electrical cable and must be 610 mm or 0.20.39¨.
INFORMATION!
The device fulfills all requirements per protection category IP 66/67. It also fulfils all
requirements per NEMA type 4X (housing) and type 6P (probe).
DANGER!
Make sure that the cable gland is watertight.
Figure 3-10: How to make the installation agree with protection category IP 67