User guide

3 ELECTRICAL CONNECTIONS
20
OPTIFLEX 2200 C/F
www.krohne.com 04/2013 - 4000861902 - AD IECEX OPTIFLEX2200 R02 en
Equipment needed (not supplied)
2.5 mm Allen wrench.
De-energize the circuit.
After the time given in the table that follows, remove the cover stop 1.
i Use a 2.5 mm allen wrench.
Remove the terminal compartment cover 2.
Ex d ia- or Ex ia tb-approved devices:
Time for the internal temperature of the housing to decrease to a safe level
3.2.2 How to close the terminal compartment
Ex i applications
Attach the terminal compartment cover 2. Turn the terminal compartment cover carefully to
prevent damage to the thread and the gasket.
Make sure that the terminal compartment cover is tight.
Ex d / Ex t applications
Attach the terminal compartment cover 2. Turn the terminal compartment cover carefully to
prevent damage to the thread and the gasket.
Make sure that the terminal compartment cover is tight.
Use a 2.5 mm Allen wrench to attach the cover stop 1.
Make sure that the cover stop 1 screw is tight.
INFORMATION!
Ex i applications
Ex i applicationsEx i applications
Ex i applications
If you remove the terminal compartment cover, the device has a degree of ingress protection
IP 20.
WARNING!
Ex d / Ex t applications
Ex d / Ex t applicationsEx d / Ex t applications
Ex d / Ex t applications
Do not remove the terminal compartment cover while the electrical power is connected.
Temperature class Time for the internal temperature of the housing to
decrease to a safe level
[minutes]
T6, T5 10
T4, T3, T2 Not necessary
DANGER!
Ex d / Ex t applications
Ex d / Ex t applicationsEx d / Ex t applications
Ex d / Ex t applications
Make sure that the terminal compartment is correctly sealed. An explosion can cause death or
injury to personnel and/or damage to equipment. Obey the instructions that follow: