User guide

2 INSTALLATION
10
OPTIFLEX 4300 C
www.krohne.com 02/2009 - 4000523601 - AD ATEX OPTIFLEX 4300 R01 en
Equipment category II 2 G: all other probe types
Equipment category II 1 D (Ex ia devices only), II 1/2 D, and II 2 D
Temperature
class
Ambient temperature Flange temperature
[°C] [°F] [°C] [°F]
T6 -40+60 -40+140 -50+60 1 -58+140 2
-40+55 -40+131 -50+85 1 -58+185 2
T5 -40+75 -40+167 -50+75 1 -58+167 2
-40+70 -40+158 -50+100 1 -58+203 2
T4 -40+85 -40+185 -50+85 1 -58+185 2
-40+80 -40+176 -50+110 1 -58+230 2
-40+75 -40+167 -50+135 1 -58+275 2
T3 -40+70 -40+158 -50+150 1 -58+302 2
-40+65 3 -40+149 4 -50+180 1 -58+356 2
-40+60 3 -40+140 4 -50+200 1 -58+392 2
1 -50°C, if an EPDM gasket is used. -40°C, if a Viton® GLT gasket is used. -20°C, if a Kalrez® 6375 gasket is used.
2 -58°F, if an EPDM gasket is used. -40°F, if a Viton® GLT gasket is used. -4°F, if a Kalrez® 6375 gasket is used.
3 if the device has an adaptor for BM 100 probes, the flange temperature must be less than 150°C
4 if the device has an adaptor for BM 100 probes, the flange temperature must be less than 300°F
Ambient temperature Flange temperature
Ø2 mm/Ø0.08¨ single
cable probe (HT version)
Ø2 mm/Ø0.08¨ single
cable probe (other
versions)
Other probes
[°C] [°F] [°C] [°F] [°C] [°F] [°C] [°F]
-40+85 -40+185 -50+300
1
-58+572
2
-50+150
1
-58+302
2
-50+200
1
-58+392
2
1 min. -50°C, if an EPDM gasket is used. Min. -20°C, if a Kalrez® 6375 gasket is used. Min. -40°C, if a Viton® GLT gasket is used.
Min. -30°C, if a Metaglas® feedthrough is used. Min. -50°C, if a PEI feedthrough is used.
2 min. -58°F, if an EPDM gasket is used. Min. -4°F, if a Kalrez® 6375 gasket is used. Min. -40°F, if a Viton® GLT gasket is used.
Min. -22°F, if a Metaglas® feedthrough is used. Min. -58°F, if a PEI feedthrough is used.
AD_ATEX_OPTIFLEX4300_en_090528_4000523601_R01_D5D.book Page 10 Thursday, May 28, 2009 6:00 PM