Installation and Operating Instructions OPTIMASS
41
Shield is connected through the cable gland.
2.4
Hazardous Area requirements
Hazardous Area Installation.
For further information please see supplementary installation and operating instructions.
Please follow these guidelines explicitly for mechanical and electrical connections.
General cabling guidelines.
To maintain the IP 67 / NEMA 4x protection it is necessary to ensure that the correct size cable is used for
the cable glands. Please ensure that the cable glands are well tightened. Provide a “drop” loop for water
to drip off.
2.5 Inputs and outputs
2.5.1 Inputs/Outputs MFC 050
The MFC 050 has many options and variations for the inputs/outputs.
The meter is shipped from the factory with one of the following options pre-configured:
Option Function
1 1 x current,1 x pulse,1 control input,1 x status output-HART
2 1 x current plus Modbus
3 Dual phase frequency output, 1 x current, 1 x control input - HART
4 2 x current, 1 x pulse, 1 x control input, HART
5 2 x current, 1 control input,1 x status output-HART
6 3 x current, 1 x pulse - HART
7 3 x current, 1 x control input - HART
8 3 x current, 1 x status output - HART
If you are not sure what option is fitted to the converter, this may be viewed at program Fct. 4.1 IO
FITTED.
On the MFC050, the inputs/outputs have a common signal ground that is galvanically isolated from the
Potential Earth (PE).
Note
HART
®
is available on the first current output except for option 2, where a communication option is already
available.