Manual

Installation and Operating Instructions OPTIMASS
59
Fct.
No
Text Description and settings
2 TEST Main Menu 2. Test functions
2.1 DISPLAY. Carry out display test
* SURE (NO). Use the key to select YES, then press (Duration of test approx.
30 sec.). Stop test at any time with the key.
2.2 CUR. OUT. 1 Test current output I
* SURE (NO). Use the key to select YES, then press . Use the key to select
test signals from the list below.
0 mA 2 mA 12 mA 16 mA 20 mA 22 mA
To exit test mode, press the key at any time.
2.3 CUR. OUT. 2 Test current output 2
see CUR. OUT. 1 above
2.4 CUR. OUT. 3 Test current output 3
see CUR. OUT. 1 Fct. 2.2 above
2.5 PULSE OUT. Test frequency output
* SURE (NO). Use the key to select YES ,then press . Use the key to select desired
pulse width from the list below:
0.05 mSec 0.4 mSec 1.0 mSec
10.0 mSec 100.0 mSec 500.0 mSec
Then press . The system now sends pulses of the required width. To stop the test press
twice.
2.6 FREQ. OUT. Test frequency output
* SURE (NO). Use the key to select YES ,then press .
* LEVEL LOW 0 volt DC level will be output from the converter.
Use the key to select test signals from the list below.
* LEVEL HIGH (+ V volts dc)
* 1 Hz * 100 Hz
* 10 Hz * 1000 Hz
2.7 ALARM OUT. Test alarm output
* SURE (NO). Use the key to select YES, then press
* LEVEL LOW. 0 Volts is output on the alarm terminal.
Press the key to switch output to:
* LEVEL HIGH . +24V dc is output on the alarm terminal.
To exit test mode, press the key at any time.
2.8 CONTROL.INP Test control input
* SURE (NO). Use the key to select YES, then press .
The actual input level, HI or LO, and the selected functions are displayed see Fct. 3.6.1
End test by pressing the key.
2.9 DIAGNOSE Submenu 2.9 Diagnose
2.9.1 TUBE TEMP. Test temperature
Start with the key. The temperature in °C or °F is displayed.
Use the key to display the temperature in °F.
End the test by pressing the key.
2.9.2 STRAIN M.T. Test strain measuring tube
Start with the key. The strain resistance in Ohms is displayed. End the test by pressing
the key.
2.9.3 STRAIN I.C. Test strain inner cylinder
Start with the key. The strain resistance in Ohms is displayed. End the test by pressing
the key.
2.9.4 TUBE FREQ. Monitor the primary head frequency
Start test with the key. End the test with the key.
2.9.5 DRIVE.ENEGY. Monitor the primary head's drive level
Start test with the key. End test with the key.
2.9.6 SENSOR A
2.9.7 SENSOR B
Monitor the amplitudes of sensor A and B
as percentage of their max. value.
Value should correspond to amplitude setting in Fct. 5.2.4
Start test with the key. End the test with the key.
2.9.8 COMM.ERROR
S
Monitor communication errors
Start test with the key. Number of communication errors since power on is displayed.
End the test with the key.
2.10 VERSIONS Submenu 2.10 Versions
2.10.1
BACKEND.SW Monitor the backend software version
Start test with the key. End test with the key.
2.10.2 BACKEND.HW Monitor the backend hardware version
Start test with the key. End test with the key.
2.10.3 FRONTEND.SW Monitor the frontend software version
Start test with the key. End test with the key.