Installation and Operating Instructions OPTIMASS
65
Fct.
No
Text Description and settings
4.8 SYS.CTROL Submenu 4.8 System control
4.8.1 FUNCTION Function for system control
* OFF (System control inactive)
* FLOW = 0 (Mass flow readings forced to zero, totaliser frozen)
* FLOW = 0/RST. (Mass flow readings forced to zero, totaliser frozen while active
but reset to zero as condition becomes inactive. Not available with Custody
Transfer Protection)
* OUTPUTS.OFF (Forces all outputs to their OFF states)
4.8.2 CONDITION Condition for triggering the above function
* DENSITY (Function is triggered if density goes outside Max or Min limits as set in
Fcts 4.8.3 and 4.8.4)
* TEMPERATUR (Function is triggered if temperature goes outside Max or Min
limits as set in Fct 4.8.3 and 4.8.4).
Function not available with Custody Transfer Protection.
4.8.3 LOW LIMIT Minimum allowable value of temperature or density selected in Fct. 4.8.2
Units: depend on function but will correspond to those set in Fct. 3.2.6 and 3.2.7
Function not available with Custody Transfer Protection.
4.8.4 HIGH LIMIT Maximum allowable value of temperature or density selected in Fct.4.8.2
Units: depend on function but will correspond to those set in Fct. 3.2.6 and 3.2.7
Function not available with Custody Transfer Protection
4.9 COMM.MODULE Submenu 4.9 Communication modules
4.9.1 PROTOCOL Display of communication protocol fitted
(OFF, SERIAL, HART, MODBUS, PROFIBUS, FF BUS or KROHNE)
4.9.2 ADDRESS Address
(not available for selection OFF and SERIAL in Fct. 4.9.1)
4.9.3 BAUDRATE Setting Baudrate (for option MODBUS in Fct. 4.9.1 only)
4.9.4 SER.FORMAT Serial format (for option MODBUS in Fct. 4.9.1 only)
4.10 CALIB I Submenu 4.10 Calibration current output 1
4.10.1 I 1 5 mA Calibration of the current output 1 for 5 mA
4.10.2 I 1 18 mA Calibration of the current output 1 for 18 mA
4.10.3 I 2 5 mA see I 1 5 mA
4.10.4 I 2 18 mA see I 1 18 mA
4.10.5 I 3 5 mA see I 1 5 mA
4.10.6 I 3 18 mA see I 1 18 mA