Quickstart EN Owner's manual

TECHNICAL DATA 4
25
OPTISWIRL 4070
www.krohne.com06/2010 - 4000122102 - QS OPTISWIRL R04 en
Operating conditions
Temperature
TemperatureTemperature
Temperature
Product -40+240°C / -40+465°F
Ambient Non-Ex: -40+85°C / -40+185°F
Ex: -40+60°C / -40+140°F
Storage -50+85°C / -58+185°F
Pressure
PressurePressure
Pressure
Product Max. 100 bar / 1450 psi; Information on higher pressures on request.
Ambient Atmosphere
Chemical properties
Chemical propertiesChemical properties
Chemical properties
Density Taken into consideration when sizing.
Viscosity < 10 cP
Reynold's number 10000...2300000
Recommended flow velocities
Recommended flow velocitiesRecommended flow velocities
Recommended flow velocities
Liquids 0.37 m/s / 0.9823 ft/s (optional up to 10 m/s / 32.8 ft/s taking cavitation
into account)
Gases and steams 2.080 m/s / 6.6262.5 ft/s
DN15: 3.045 m/s / 9.8148 ft/s; DN25: 2.070 m/s / 6.6230 ft/s
For detailed information, see chapter "Flow tables".
Other conditions
Other conditionsOther conditions
Other conditions
Protection category IP 66/67
Installation conditions
Inlet run 20 x DN (without disturbing flow, after pipe narrowing, after a single 90°
bend)
30 x DN (after a double bend 2x90°)
40 x DN (after a double three-dimensional bend 2x90°)
50 x DN (after control valves)
2 DN before flow straightener; 8 DN after flow straightener (specified
values apply only to original 20 DN inlet run)
Outlet run 5 x DN
Dimensions and weights For detailed information refer to chapter "Dimensions and weights".
Materials
Measuring sensor and process
connections
Standard: 1.4404/316L
Option: Hastelloy
®
C-22 on request
Converter housing Die-cast Aluminium
Pressure sensor gasket Standard: FPM
Option: FFKM
Measuring tube gasket Standard: 1.4435/316L
Option: Hastelloy
®
C-276
Selection depends on measuring sensor material/medium.
QS_OPTISWIRL4070_R04_en_122102_PRT.book Page 25 Monday, June 7, 2010 8:51 AM