Instruction Manual

2
1
Fig. 5: Orientation of the tuning fork in case of ow
1 Marking with screwed version
2 Direction of ow
In case of horizontal mounting in adhesive products, the
surfaces of the tuning fork should be vertical in order to reduce
buildup on the blades. On the screwed version you will nd a
marking on the hexagon. With this, you can check the position
of the tuning fork when screwing it in. When the hexagon
touches the seal, the thread can be still turned by approx. half
a turn. This is sucient to reach the recommended installation
position.
1
Fig. 6: Vertical installation - marking
1 Marking on top with screwed version
Adhesive products
12 OPTISWITCH 3000 C - with NAMUR output
Mounting
31355-EN-060830