Operating Instructions OPTISWITCH 3100 C with two-wire output
Contents Contents 1 About this document 1.1 1.2 1.3 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. .. 5 5 5 5 6 6 Configuration. . . . . . . Principle of operation . Operation . . . . . . . . . Storage and transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. 7 7 8 9 . . . . . . . . . . . . . . . . General instructions. . . . . . . . . . . . . . . . .
Contents 9 Supplement 9.1 9.2 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . 28 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Supplementary operating instructions manuals Information: OPTISWITCH 3100 C is available in different versions. Depending on the selected version, supplementary operating instructions manuals may also come with the shipment. The supplementary operating instructions manuals are listed in section "Product description.
About this document 1 About this document 1.1 Function This operating instructions manual has all the information you need for quick setup and safe operation. Please read this manual before you start setup. 1.2 Target group This operating instructions manual is directed to trained, qualified personnel. The contents of this manual should be made available to these personnel and put into practice by them. 1.3 Symbolism used Information, tip, note This symbol indicates helpful additional information.
For your safety 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer. 2.2 Appropriate use OPTISWITCH 3100 C is a sensor for level detection.
For your safety 2.6 SIL conformity OPTISWITCH 3100 C fulfills the requirements of functional safety according to IEC 61508/IEC 61511. You can find further information in the supplementary instructions manual "Safety Manual - Functional safety (SIL) OPTISWITCH 3XXX". 2.7 Safety instructions for Ex areas Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Exapproved instruments.
Product description 3 Product description 3.
Product description It functions even when exposed to strong external vibration or changing products. Solid detection in water If OPTISWITCH 3100 C was ordered for detection of solids in water, the tuning fork is adjusted to the density of water. In the air or when covered by water (density: 1 g/cm³/0.036 lbs/in) OPTISWITCH 3100 C signals "uncovered". Only if the vibrating element is also covered with solids (e.g. sand, sludge, gravel etc.) will the sensor signal "covered".
Product description 3.4 Storage and transport Packaging Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN 55439. The packaging of standard instruments consists of environment-friendly, recyclable cardboard. In addition, the sensor is provided with a protective cover of cardboard. For special versions PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Mounting 4 Mounting 4.1 General instructions Switching point In general, OPTISWITCH 3100 C can be mounted in any position. The instrument must be mounted in such a way that the vibrating element is at the height of the requested switching point. Moisture Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland.
Mounting Handling The vibrating level switch is a measuring instrument and must be treated accordingly. Bending the vibrating element will destroy the instrument. Warning: The housing must not be used to screw in the instrument! Applying tightening force on the housing can damage its internal mechanical parts. To screw in, use the hexagon above the thread. 4.2 Mounting instructions Socket The vibrating element should protrude into the vessel to avoid buildup.
Mounting In abrasive solids, mounting according to illustration b. has proven. A spout forms in the concave protective sheet preventing wear of the protective sheet. Horizontal mounting To achieve a very precise switching point, you can install OPTISWITCH 3100 C horizontally. However, if the switching point can have a tolerance of a few centimeters, we recommend mounting OPTISWITCH 3100 C approx. 20° inclined to the vessel bottom to avoid buildup. a. b. 20° Fig.
Mounting 1 2 Fig. 5: Orientation of the tuning fork in case of flow 1 Marking with screwed version 2 Direction of flow Adhesive products In case of horizontal mounting in adhesive products, the surfaces of the tuning fork should be vertical in order to reduce buildup on the blades. On the screwed version you will find a marking on the hexagon. With this, you can check the position of the tuning fork when screwing it in. When the hexagon touches the seal, the thread can be still turned by approx.
Mounting >125 Fig.
Connecting to voltage supply 5 Connecting to voltage supply 5.1 Preparing the connection Note safety instructions Generally not the following safety instructions: l Connect only in the complete absence of line voltage Take note of safety instructions for Ex applications In hazardous areas you should take note of the appropriate regulations, conformity and type approval certificates of the sensors and power supply units. Select power supply Connect the power supply according to the following diagrams.
Connecting to voltage supply 3 Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.
Connecting to voltage supply Housing overview 4 4 1 Fig. 1 2 3 4 4 2 3 9: Material versions, single chamber housing Plastic (not with EEx d) Aluminium Stainless steel (not with EEx d) Filter element for pressure compensation (not with EEx d) Electronics and connection compartment 1 5 2 4 3 Fig.
Connecting to voltage supply l l red - with submerged vibrating element green - with uncovered vibrating element Take note of the operating instructions manual of the signal conditioning instrument. Suitable signal conditioning instruments are listed in the "Technical data". 1 Fig.
Set up 6 Set up 6.1 General The numbers in brackets refer to the following illustrations. Function/Configuration On the electronics module you will find the following indicating and adjustment elements: l l l Potentiometer for switching point adaptation (1) DIL switch for mode adjustment - min./max. (2) Signal lamp (5) Note: As a rule, always set the mode with mode switch (2) before starting the setup of OPTISWITCH 3100 C .
Set up 6.2 Adjustment elements 1 5 2 4 3 Fig. 1 2 3 4 5 Switching point adaptation (1) 12: Oscillator WE60Z - two-wire output Potentiometer for switching point adaptation DIL switch for mode adjustment Ground terminal Screwed terminals Control lamp With the potentiometer you can adapt the switching point to the solid. It is already preset and must only be modified in special cases. By default, the potentiometer of OPTISWITCH 3100 C is set to the right stop (>0.02 g/cm³ or >0.0008 lbs/in³).
Set up min. - min.detection or dry run detection) on the signal conditioning instrument. When used on a control system, the following values apply: l Mode min. - Vibrating element uncovered - 16 mA ±1 mA - Vibrating element covered - 8 mA ±1 mA l Mode max. - Vibrating element uncovered - 8 mA ±1 mA - Vibrating element covered - 16 mA ±1 mA Control lamp for indication of the switching condition. Signal lamp (5) l l l green = 8 mA red = 16 mA red (flashing) = Failure (<2.3 mA) 6.
Set up Mode on the sensor Level Signal current - Sensor Fault signal (min./max. mode) any Signal lamp - sensor <2.3 mA flashes red OPTISWITCH 3100 C level switch with signal conditioning instrument1) The following chart provides an overview of the switching conditions depending on the adjusted mode of the signal conditioning instrument and the level. Note: Keep in mind that the mode switch of OPTISWITCH 3100 C must be always set to "max.".
Set up Mode on the signal conditioning instrument Fault signal (mode A/B) Level Signal current Sensor any Signal lamp - sensor Signal lamp - signal conditioning instrument <2.
Maintenance and fault rectification 7 Maintenance and fault rectification 7.1 Maintenance When used as directed in normal operation, OPTISWITCH 3100 C is completely maintenance free. 7.2 Rectify faults Causes of malfunction OPTISWITCH 3100 C offers maximum reliability. Nevertheless faults can occur during operation. These may be caused by the following, e.g.: l l l l Sensor Process Power supply Signal processing Fault rectification The first measure to be taken is to check the output signal.
Maintenance and fault rectification l Wrong mode selected à Set the mode switch on OPTISWITCH 3100 C to "max". Set the correct mode on the signal conditioning instrument (A: overfill protection; B: dry run protection). ? Signal lamp flashes red l Electronics has detected a failure à Exchange instrument or return instrument for repair 7.3 Exchange the electronics In general, all oscillators of series WE60 can be interchanged.
Maintenance and fault rectification 6 Remove the old oscillator 7 Compare the new oscillator with the old one. The type label of the oscillator must correspond to that of the old oscillator. This applies particularly to instruments used in hazardous areas. 8 Compare the settings of the two oscillators. Set the adjustment elements of the new oscillator to the same setting of the old one. Information: Make sure that the housing is not rotated during the electronics exchange.
Dismounting 8 Dismounting 8.1 Dismounting procedure Warning: Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. With Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present. 8.
Supplement 9 Supplement 9.1 Technical data General data Material 316L corresponds to 1.4404 or 1.4435 Materials, wetted parts - Process fitting - thread 316L - Process fitting - flange 316L - Process seal Klingersil C-4400 - Tuning fork 316L - Extension tube ø 43 mm (1.
Supplement Integration time - when immersed approx. 0.5 s - approx. 1 s when laid bare Ambient conditions Ambient temperature on the housing -40 … +80 °C (-40 … +176 °F) Storage and transport temperature -40 … +80 °C (-40 … +176 °F) Process conditions Parameter Limit level of solids Process pressure -1 … 16 bar/-100 … 1600 kPa (-14.5 … 232 psi) 2 16 bar (232psi) 6 bar (87psi) -50˚C (-58˚F) 0˚C (32˚F) 1 50˚C (122˚F) 100˚C (212˚F) 150˚C (302˚F) 200˚C (392˚F) 250˚C (482˚F) Fig.
Supplement 2 3 80˚C (176˚F) 40˚C (104˚F) -50˚C (-58˚F) 1 0˚C (32˚F) 50˚C (122˚F) 100˚C (212˚F) 150˚C (302˚F) 200˚C (392˚F) 250˚C (482˚F) -40˚C (-40˚F) Fig. 1 2 3 15: Ambient temperature - Product temperature Product temperature Ambient temperature Temperature range with temperature adapter Density - Standard >0.02 g/cm³ (0.0007 lbs/in³) - adjustable >0.008 g/cm³ (0.0003 lbs/in³) Electromechanical data Cable entry/plug2) - Single chamber housing l or: l 1x cable entry M20x1.
Supplement Voltage supply Supply voltage 10 … 36 V DC (via the signal conditioning instrument) Electrical protective measures Protection IP 66/IP 67 Overvoltage category III Protection class II Approvals3) ATEX II 1G, 1/2G, 2G EEx ia IIC T64) ATEX II 1G, 1/2G, 2G EEx ia IIC T6 + ATEX II 1/2 D IP66 T ATEX II 1/2G, 2G EExd d IIC T6 29955-EN-060830 ATEX II 1/2 D IP66 T5) 3) 4) 5) Deviating data in Ex applications: see separate safety instructions.
Supplement 9.2 Dimensions OPTISWITCH 3100 C ~ 69mm (2 23/32") 1 Fig.
22mm (55/64") 33mm (1 19/64") Supplement G1½A 220mm (8 21/32") 150mm (5 29/32") ø 43mm (1 11/16") 29955-EN-060830 Fig.
178mm (7 1/64") Supplement ø 34mm (1 11/32") Fig.
29955-EN-060830 Supplement OPTISWITCH 3100 C - with two-wire output 35
Subject to change without notice 29955-EN-060830