User Manual

6 Set up
6.1 General
The numbers in brackets refer to the following illustrations.
On the electronics module you will nd the following indicating
and adjustment elements:
l Potentiometer for switching point adaptation (1)
l DIL switch for mode adjustment - min./max.(2)
l Signal lamp (5)
Note:
As a rule, always set the mode with mode switch (2) before
starting the setup of OPTISWITCH 3100 C . If the instrument is
used in conjunction with a signal conditioning instrument,
always set the mode switch (2) on OPTISWITCH 3100 C to
max. mode.
The mode is selected on the signal conditioning instrument
with the mode switch.
The switching output will change if you set one of the two mode
switches afterwards. This could possibly trigger other con-
nected instruments or devices.
Function/Conguration
OPTISWITCH 3100 C - with two-wire output 19
Set up