7.3 Exchange the electronics
To exchange the electronics in case of failure, it is not
necessary to dismount the instrument.
Dismounting the electronics module can destroy the housing
seal. Therefore only open the instrument if you want to insert a
new electronics module. The housing seal is supplied with the
electronics module.
You need an electronics module type SWE50T or SWE50C. If
you want to use an electronics module with a dierent signal
output (e.g. transistor output SWE50T), you can download the
suitable operating instructions manual from our homepage
under Downloads. Take note of the specications in the
respective operating instructions manual.
To exchange the electronics module, proceed as follows:
1 Separate OPTISWITCH 4000 C from operating voltage
2 Loosen xing screw (1) of the valve plug (2) with a wrench
3 Remove valve plug (2) acc. to drawing
4 Remove lateral xing screw (7) with a crosstip screwdriver
5 P
ull electronics module (4) carefully out of the housing (8)
6 Remove the plug of the connection cable (6) from the
socket on the oscillator (4)
7 Set the 16-step rotating switch (5) of the new replacement
electronics module (4) to the value of the defective
electronics module
8 Insert the connection cable (6) in the socket of the new
electronics module (4)
9 Insert electronics module (4) into the housing (8). Make
sure that the lateral thread on the electronics module is
above the hole on the housing (8)
10 Push the electronics module (4) ush into the housing (8)
11 Screw in the lateral xing screw (7) with a crosstip
screwdriver
12 Plug the valve plug (2) to the instrument, make sure that
the prole seal (3) is placed correctly
13 T
ighten xing screw (1) with a wrench
OPTISWITCH 4000 C is again ready for operation.
OPTISWITCH 4000 C - with contactless electronic switch 21
Maintenance and fault rectication