User guide

6 Set up
6.1 General
The numbers in brackets refer to the following illustrations.
The switching condition of the electronics can be checked on
the plastic housing with closed housing cover (control lamp). In
the basic setting, products with a density >0.7 g/cm³
(>0.025 lbs/in³) can be detected. For products with lower
density, the switch must be set to >0.5 g/cm³ (>0.018 lbs/in³).
On the electronics module you will nd the following indicating
and adjustment elements:
l Signal lamp (1)
l DIL switch for characteristics reversal - min./max.(2)
l DIL switch for sensitivity adjustment (3)
l Simulation key (4)
Note:
For test purposes, immerse the tuning fork of OPTISWITCH
5200 C, 5250 C always in liquids. Do not test the function of
OPTISWITCH 5200 C, 5250 C with the hand. This can
damage the sensor.
6.2 Adjustment elements
1
2
1
2
3
4
Fig. 13: Oscillator SWE60N - NAMUR output
1 Signal lamp (LED)
2 DIL switch for characteristics reversal
3 DIL switch for sensitivity adjustment
4 Simulation key
Function/Conguration
OPTISWITCH 5200 C, 5250 C - with NAMUR output 19
Set up
30434-EN-060831