Owner's manual

7 TECHNICAL DATA
52
OPTITEMP TRA/TCA
www.krohne.com 08/2010 - 4000630501 - MA OPTITEMP TRA/TCA R01 en
7.4 Measuring accuracy
The measuring accuracy depends largely on the following factors:
The version of the measuring insert (type of sensor, type of circuit, measuring range).
The correct dimensions (diameter, wall thickness) and insertion length of the thermowell for
good thermal coupling to the process temperature (insufficient insertion depth often results
in measurement errors).
The type of temperature transmitter used.
With the exception of the TT 60 C/R version, all of the temperature transmitters generate an
analogue output signal. For this reason, the following table indicates the measuring accuracy of
most of the transmitters as a percentage of the measuring range:
Temperature transmitter
INFORMATION!
Please consult the appropriate handbook for further information regarding the accuracy of the
measuring inserts and the temperature transmitters.
Type of temperature transmitter Accuracy (% of the measuring range or °K)
TT 10 C/R (analogue, standard) ± 0.15%
TT 11 C/R (analogue, voltage output) ± 0.15%
TT 20 C/R (analogue) ± 0.10%
TT 30 C/R (digital, standard) ± 0.10%
TT 40 C/R (digital, precise) ± 0.05%
TT 50 C/R (digital, HART
®
)
± 0.10%
TT 51 C (digital, HART
®
, SIL2)
± 0.05%
TT 60 C/R (digital, Profibus) ± 0.10°K
.book Page 52 Tuesday, August 17, 2010 12:18 PM