ELECTRICAL CONNECTIONS 4
53
OPTIWAVE 5200 C/F
www.krohne.com07/2013 - 4001904902 - HB OPTIWAVE 5200 R02 en
Make sure that the gaskets are not damaged.
Make sure that the electrical cables are not damaged.
Make sure that the electrical cables agree with the national electrical code.
The cables are in a loop in front of the device 1 so water does not go into the housing.
Tighten the cable feedthroughs 2.
Close unused cable feedthroughs with dummy plugs 3.
The diameter of the outer sheath of the electrical cable and must be 610 mm or 0.20.39¨.
4.6 Networks
4.6.1 General information
The device uses the HART
®
communication protocol. This protocol agrees with the HART
®
Communication Foundation standard. The device can be connected point-to-point. It can also
operate in a multi-drop network of up to 15 devices.
The device output is factory-set to communicate point-to-point. To change the communication
mode from point-to-point
point-to-pointpoint-to-point
point-to-point to multi-drop
multi-dropmulti-drop
multi-drop, refer to
HART
® network configuration on page 78.
4.6.2 Point-to-point connection
Figure 4-14: Point-to-point connection (non-Ex)
1 Address of the device (0 for point-to-point connection)
2 4...20 mA + HART
®
3 Resistor for HART
®
communication
4 Power supply
5 HART
®
converter
6 HART
®
communication software