6 OPERATION
80
OPTIWAVE 5200 C/F
www.krohne.com 07/2013 - 4001904902 - HB OPTIWAVE 5200 R02 en
6.4.6 Level measurement
The device displays level measurements when the output function is set to "Level".
Menu items related to level measurement are:
Output Function (2.4.1)
Tank Height (2.3.1)
Blocking Distance (2.3.2)
For more data about the menu items, refer to
Function description
on page 68, table 2:
Supervisor menu.
CAUTION!
If the level for the 20 mA is set in the blocking distance, the device will not be able to use the full
current output range.
Figure 6-5: Level measurement
1 Tank Height (2.3.1)
2 Blocking Distance (2.3.2)
3 Maximum effective measuring range
4 20 mA Setting (2.4.4)
5 4mA Setting (2.4.3)
6 Non-measurement zone