User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 User Guide Optiwave (FMCW) Device Asset Management Solutions (AMS) HART Communicator 375 Version 1.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 Table of Contents 1 2 3 4 5 HART® Transmitter Revisions and Instrument Firmware ............................................................................................................ 3 1.1 Device Revision....................................................................................................................................................................... 3 1.2 DD Revision .................................................
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 1 HART® Transmitter Revisions and Instrument Firmware 1.1 Device Revision The Optiwave HART® transmitter has only one revision: Device revision 1. 1.2 DD Revision Optiwave 7300C has the DD revision 2. DD is tested with AMS 9.0. 2 Installation of DLL in AMS Refer to the AMS help to install the device (Optiwave 7300C) into an AMS System. 3 Menu 3.1 Access Rights 3.1.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.1.2 Supervisor Password On clicking Supervisor it shows the following screen. Note: Before accessing this menu user needs to select the “configuration variables” for synchronization of all device parameters and for proper validation of the device parameters. On clicking next, it shows the following window, which asks user to enter the Supervisor Password with the default value as 65535.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 After entering the valid password and clicking next, it shows the following screen: For success: “Supervisor Password OK” For invalid password: “Supervisor Password Invalid” 3.1.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.2 Save Device Parameters ATTENTION: This is a very important method. Each time the device configuration is modified (after applying changes) it is necessary to execute this method. Otherwise the modifications will not be taking into account.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.3 Diagnostic and Test 3.3.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 © 2006 KROHNE SAS 26103 Romans (France) Page 8 of 34
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.3.2 Set Output1 It allows fixing different values to the current output1 . It is a test mode. User can check the loop currents in output1 and output2. The list of currents are displayed in the list box. Once the appropriate current is selected the loop current is fixed to that current value. Check the loop current by ammeter and validates the current as selected from the device.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.3.3 Set Output2 See “Set Output1” 3.4 Calibration The Calibration can be done for the output1 and output2. Here the following sections will be describes the detailed about the calibration screen options for the output1 lower and upper. 3.4.1 Output1 Lower In Output1 Lower, it allows user to trim current output1.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 © 2006 KROHNE SAS 26103 Romans (France) Page 11 of 34
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.4.2 Output1 Upper In Output1 Upper, user allows to trim current output1. The user start to fix the current to 20mA, after entering the current value he read on a voltmeter, this value is sent to the device. This method allows adjusting to have exactly the good current value of output1 loop.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 © 2006 KROHNE SAS 26103 Romans (France) Page 13 of 34
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.5 Tables 3.5.1 Volume/Mass Table Select “Conversion Table” will display all the entries of conversion table in ‘2 x 2’ Format. Display will be in following steps 1. After Displaying all entries: If yes is selected, it permits user to edit or add new entries.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 2. Selection of Next Entry will show next entry Level to edit, after clicking Enter, Volume/Mass is displayed for next Entry to edit. After editing Level & Volume/Mass for current entry, above shown menu is displayed again. 3. Selection of Previous Entry will show previous entry Level to edit, after clicking next, Volume/Mass is displayed for previous Entry to edit.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.5.2 Linearisation Table Above explained steps for volume/mass Table are to be followed, with Distance Real, Distance Device instead of Level and Volume respectively. The editing and displaying wizard is the same as that of volume/mass table .
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.5.3 Delete Tables Delete tables allow user to delete the volume/mass and Linearisation tables entirely.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.6 Empty Spectrum Recording The following figure in order illustrates the steps for Empty Spectrum Recording.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 After validating all the depending parameters required for the empty spectrum process, It starts the recording, displaying the current status of it.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.7 Reset There are three types of reset. For the security reasons it re-ensures for the reset. 3.7.1 Factory Reset In the Factory Reset, the device or configurations are set to the factory default values.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.7.2 Customer Reset This makes the parameter values to user default values.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.7.3 Device Reset It is used to restart the device.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8 Configuration Variables To view Help for each configuration parameter, first click on Help button on toolbar & then click on the parameter for which help is to be viewed. 3.8.1 Installation Parameters1 This plate consists of the editable parameters of the device like Tank Type, Tank Height etc.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8.2 Installation Parameters2 It allows user to change the unit of configuration parameters.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8.3 Output Selection It allows user to change the Primary Output Function, Secondary Output Function, Tertiary Output Function and Fourth Output function. Beside this it provides detail’s of primary and secondary output as differentiated by the group box namely output1 and output2.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8.4 Primary Output Setting It allows user to change the upper and lower limit of the parameters set in the output selection plate for the primary output function. The units of all these parameters are shown as set in the installation plate2. Since only one pair of parameters can be set to the primary output function, hence the rest of the parameters are disabled.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8.5 Secondary Output Setting It allows user to change the upper and lower limit of the parameter set in the output selection plate for the secondary output function.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8.6 Service It allows user to view all the service parameters, calibration parameters and the service information. The service parameters are only activated by the service password.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8.7 HART It shows all the hart related parameters viz: manufacturer name, model name etc.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.8.8 Device It shows the device specific information. This plate doesn’t require any authentication. All the parameters can be viewed with no password.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.9 Process Variable The Process Variables are displayed with magnitude and its corresponding unit along with upper & lower limits. Four process variables are active on a single screen depending on the Output function setting.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 3.10 Device Diagnostic It contains the status of the device.
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 4 Status Meaning Status Message Supervisor Password OK Supervisor Password Invalid Simulation Service Password OK Service Password Invalid Service Password OK Simulation Supervisor Password OK Dependency failure Update not possible Reading data from device Dependency Warning Message Max range failure Min range failure Table entered is not monotonous Device busy Access Restricted Invalid Section Too Few Bytes Received Invalid Command Reques
User Guide for Optiwave (FMCW) DD of AMS Dev Rev-01, DD Rev-02 Illegal character If any invalid character is entered. Max range failure occurred writing level It appears if entered Value for 20mA is 20mA.Restore device value out of range. Method is currently invalid It appears if access right is not 5 HART® Communicator 375 (HC375) 5.1 Offline Restriction In order to transfer an Offline configuration to the device the Service parameter “Supervisor Password Enable” (C.5.2.0) must be set to “NO”.