4 ELECTRICAL CONNECTIONS
28
TIDALFLUX 2300 F
www.krohne.com 06/2013 - 4002490202 MA TIDALFLUX 2300 F R02 en
4.9 Interface cable
The data interface cable is a shielded, 3 x 1.5 mm
2
LIYCY cable.
1 Strip the conductor to dimension a.
2 Trim the outer shield to dimension b and pull it over the outer sheath.
3 Crimp the wire end ferrules onto the conductors 1, 2 and 3.
Connect the shielding at both sides of the cable via the special cable gland.
Preparing the interface cable
Figure 4-16: Preparing the interface cable
a = 100 mm / 4"
b = 10 mm / 0.4"