User Manual
TECHNICAL DATA 6
37
TIDALFLUX 2300 F
www.krohne.com06/2013 - 4002490202 MA TIDALFLUX 2300 F R02 en
Electrical connections
General Electrical connection is carried out in conformity with the VDE 0100
directive "Regulations for electrical power installations with line
voltages up to 1000 V" or equivalent national specifications.
Power supply Standard: 100...230 VAC (-15% / +10%), 50/60 Hz
Option 1: 24 VAC/DC (AC: -15% / +10%, 50/60 Hz; DC: -25% / +30%)
Power consumption AC: 22 VA
Field current cable Shielded cable must be used, no part of delivery.
Signal cable DS 300 (type A)
DS 300 (type A)DS 300 (type A)
DS 300 (type A)
Max. length: 600 m / 1950 ft (dependent on electrical conductivity).
BTS 300 (type B)
BTS 300 (type B)BTS 300 (type B)
BTS 300 (type B)
Max. length: 600 m / 1950 ft
Data interface cable For transmission of measured level to IFC 300 F.
Shielded Liycy cable, 3 x 0.75 mm
2
Cable entries Standard: 2x M20 x 1.5 + 2x M16 x 1.5 EMC type
Option: ½" NPT
Approvals and certificates
CE
CECE
CE
This device fulfills the statutory requirements of the EC directives.
The manufacturer certifies successful testing of the product by
applying the CE mark.
Electromagnetic compatibility Directive: 2004/108/EC, NAMUR NE21/04
Harmonized standard: EN 61326-1 : 2006
Low voltage directive Directive: 2006/95/EC
Harmonized standard: EN 61010 : 2001
Pressure equipment directive Directive: 97/23/EC
Category I, II or SEP
Fluid group 1
Production module H
Hazardous areas
Hazardous areasHazardous areas
Hazardous areas
ATEX Option: Ex zone 1, IECex
Other approvals and standards
Other approvals and standardsOther approvals and standards
Other approvals and standards
Protection category acc. to
IEC 529 / EN 60529
Standard: IP 66/67 (NEMA 4/4X/6)
Option: IP 68 (NEMA 6P)
Vibration resistance IEC 68-2-6
Random vibration test IEC 68-2-34
Shock test IEC 68-2-27