3 ELECTRICAL CONNECTIONS
20
TIDALFLUX 4300 F
www.krohne.com 09/2010 - 7308302300 - QS TIDALFLUX 4000 R03 en
At flow converter side:
At flow sensor side:
Connecting shielding under clamp in connection box of converter
Figure 3-9: Clamping of shields
1 Field current cable
2 Signal cable
Connecting shielding via special cable gland
Figure 3-10: Connecting the shield within the cable gland
1 Wires
2 Isolation
3 Shielding
4 Isolation
5 Feed cable through dome nut and clamping insert and fold shielding over clamping insert. Make sure that the braided
shield overlaps the O-ring by 2 mm / 3/32".
6 Push clamping insert into body.
7 Tighten the dome nut.