© KROHNE 09/2004 Supplementary Installation and Operating Instructions HART Communicator 275 Field Communicator 375 Asset Management Solutions (AMS) Process Device Manager (PDM) UFC 030 Ultrasonic Flow Converter KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM 1 General Information 3 2 IDs and Revision numbers 5 3 HART Communicator 275 (HC275), Field Communicator 375 (FC375) 6 4 5 3.1 Installation 6 3.2 Operating 6 Asset Management Solutions (AMS) 6 4.1 Installation 6 4.2 Operating 6 Process Device Manager (PDM) 7 5.1 Installation 7 5.2 Operating 7 KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM 1 General Information The UFC 030 is a “four-wire” transmitter with 4...20mA current output and HART capability. Dependent on device implementation it is available with active/passive current output (standard) or passive current output (MODIS).
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM b) As a multipoint connection (multidrop) with up to 15 devices (UFC 030 or other HART equipment) in parallel. The instrument's current outputs must be passive. Multidrop Mode Primary Master HART Modem HART Power Supply ≥ 250 Ω Terminal I/C 4 mA 4 mA Terminal ⊥ ... Secondary Master Up to 15 Slaves ... UFC 030 Addr. > 0 UFC 030 Addr.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM In case the UFC 030's current output shall work continuously active a 'third wire' is needed to properly connect it together with two-wire loop powered devices in the same network. Multidrop Mode (‘three-wire’) (Connecting two-wire and four-wire devices in the same network) Primary Master HART 4 mA HART Modem 4 mA two-wire loop powered devices ... Addr. > 0 Power Supply Addr.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM 3 HART Communicator 275 (HC275), Field Communicator 375 (FC375) 3.1 Installation The UFC 030 HART Device Description has to be installed on the HC275 and FC375 respectively. Otherwise the user will work with the instrument as a generic one thus loosing opportunity for entire instrument control.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM 5 Process Device Manager (PDM) 5.1 Installation If the UFC 030 Device Description is not already installed on the PDM System a so called Device Install is needed (available as download from KROHNE ‘Download Centre’ on the internet or on floppy disk / CD-ROM from KROHNE). For installing the DD with the Device Install refer to the “PDM Manual” section 11.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM Attachment A UFC 030 HART Menu Tree HC275 / FC375 1 Dynamic Variables 1 View Process Vars 1 Actual Flow 2 Corrected Flow Opt 3 VOS 4 Analog Input 1 Opt 5 Analog Input 2 Opt 6 F/R Indication 7 Gain 8 Digital Output Opt 9 Totalizer 1 Opt 10 Totalizer 2 Opt 11 Totalizer Sum Opt 1 Function I 2 Value I 3 %Range I 4 Function P Opt 5 Value P Opt 6 %Range P Opt 7 Analog Input 1 Opt 8 Analog Input 2 Opt 2 View In/Outputs 1
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree HC275 / FC375 1 Dynamic Variables 1 1 Test / Info 2 Configuration / Test 1 1 Flow Units 2 Full Scale 3 Zero Value 4 Zero Calibration Opt 5 Master TC 6 L.F.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree HC275 / FC375 1 Dynamic Variables 1 1 Test / Info 2 Configuration / Test 1 2 Installation 1 Flow 2 Version 3 Display 4 Current Output I 5 Pulse Output P 6 User Data 3 Service Menu 3 Quit/Reset 4 HART Variables 1 1 Function I 2 Direction I 3 Range I 4 I 0% 5 I 100% 6 Limit 1 Function P Opt 2 Direction P Opt 3 Digital Output Opt 4 Trip.Point 1 Opt 5 Trip.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree HC275 / FC375 1 Dynamic Variables 1 2 Configuration / Test 1 Test / Info 1 2 Installation 2, 3 3 Service Menu 5 1 Quit Errors 2 Reset Totalizers Opt 3 Master Reset 4 Reset Conf. Flag 3 Quit/Reset 1 Communication 1 Poll addr 2 Num req preamsRd 3 Num resp preams 2 Device inform.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree HC275 / FC375 1 Dynamic Variables 1 1 Test / Info 2 Installation 2 Configuration / Test 3 Service Menu 1 2, 3 1 Service Code 2 System Opt 3 Current Output I Opt 4 Sensor Opt 5 Measuring Path Opt 6 An. Inp. Calib.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM Attachment B UFC 030 HART Menu Tree AMS Basic Setup Sensor • Zero Value • Flow Direction Process Input • Flow Units • Full Scale • Master TC • L.F.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree AMS Measuring Path • Path 1 active ... • Weight 1 ... • Length 1 ...
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree AMS Overview • Primary variable out of limits • Non-primary variable out of limits • Primary variable analog output saturated • Primary variable analog output fixed • Cold start • Configuration changed • Field device malfunction 1 • • • • • • • Path 1 Signal Failure … Path 3 Signal Failure Sensor open Sensor short circuit Unreliable Empty Pipe Error • • • • • • • • • Signal Proc. Contr.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM Attachment C UFC 030 HART Menu Tree PDM Menu Bar File Communication Path ----------------------------------Load To Device Load To PG/PC ----------------------------------Set Address ----------------------------------Simulation Device View Help 2,3 Simulation • Simulation Mode • Uncorrected Flow • VOS • Gain • Analog Input 1 Opt • Analog Input 2 Opt Test Inputs Opt • Analog Input 1 • Analog Input 2 Test Options
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree PDM Menu Bar 1 File Device View Measured Values • Actual Flow • Corrected Flow Opt • VOS • F/R Indication • Gain • Digital Output Opt Display Options Help Totalizer Opt • Totalizer 1 Opt • Totalizer 2 Opt • Totalizer Sum Opt Analog InputsOpt • Analog Input 1 • Analog Input 2 Raw Values Opt • Relative Flow Speed 1 ... 3 Opt • SOS 1 ... 3 Opt • Gain 1 ...
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree PDM Menu Bar 1 File Device Display Yt Diagram Outputs/Inputs 2 View Device Device Info • Manufacturer Rd • Model Number Rd • Serial Number Rd • µP1 HW No. Rd • µP2 SW No. Rd • FE HW No. Rd • DSP HW No. Rd • DSP SW No.
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree PDM Parameter Table Identification Identification Operation Unit Input ...
Supplementary Installation and Operating Instructions UFC 030 HART HC275, FC375, AMS, PDM UFC 030 HART Menu Tree PDM Parameter Table Output • IO Fitted Rd Identification Operation Unit Device 4 ----------------------------------Input Measuring Limits Operation Parameter Sensor Version Analog Input Opt 4 Measuring Path Opt Plausibility Filter ----------------------------------Output Current Output I Pulse Output P Opt ----------------------------------Human Interface Local Display Display Formats Curr