OPERATION 4
39
UFC 400
www.krohne.com05/2013 - 4002813701 - AD FF UFC 400 R01 en
4.6 FLOWTB (Flow Transducer Block)
Parameter
ParameterParameter
Parameter
DD name
Access Description and settings Initial Value
ALERT_KEY
ALERT_KEYALERT_KEY
ALERT_KEY
Alert Key
R/W The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
0
Setting:
1...255
BLOCK_ERR
BLOCK_ERRBLOCK_ERR
BLOCK_ERR
Block Error
R This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
Other
Setting:
Other: Non-specific error active
Block Configuration: Error detected in block configuration
Link Configuration: Error detected in link configuration
Simulation Active: Simulation enabled in this block
Local Override: Output tracking of faultstate active
Device Fault State: Device faultstate set
Device Maintenance: Device needs maintenance soon
Input Failure: Process variable has bad status
Output Failure: Failure detected in output hardware
Memory Failure: Memory error detected
Lost Static Data: Static parameters cannot be recovered
Lost NV Data: Non-volatile parameters cannot be recovered
Readback Check: Failure detected in READBACK
Maintenance Needed: Device NEEDS maintenance NOW
Power Up: Recovery from power failure
Out Of Service: Block actual mode is out of service
MODE_BLK
MODE_BLKMODE_BLK
MODE_BLK
Block Mode
The actual, target, permitted and normal modes of the block. -
TARGET
Target
R/W This is the mode requested by the operator. Only one mode
from those allowed by the permitted mode parameter may be
requested.
Auto
Setting:
Auto / OOS
ACTUAL
Actual
R This is the current mode of the block, which may differ from
the target based on operating conditions. Its value is
calculated as part of block execution.
Auto
Setting:
Auto / OOS
PERMITTED
Permitted
R/W Defines the modes which are allowed for an instance of the
block. The permitted mode is configured based on application
requirement.
Auto
OOS
Setting:
Auto / OOS
NORMAL
Normal
R/W This is the mode which the block should be set to during
normal operating conditions.
Auto
Setting:
Auto / OOS
ST_Rev
ST_RevST_Rev
ST_Rev
Static Revision
R The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
0
Setting:
0...65535