User guide

ELECTRICAL CONNECTIONS 3
5
UFC 400
www.krohne.com05/2013 - 4002813701 - AD FF UFC 400 R01 en
3.1 Cable types
The cable types are specified according to IEC 61158-2. Shielded cables offer the advantage of
malfunction-free operation with adequate protection against electromagnetic influences, and
make it possible to employ the full performance of the Foundation Fieldbus system.
In non-hazardous locations, a maximum of 32 field devices can be connected to the network. For
more data, refer to the table that follows.
All bus segments must be fitted with a terminator at both ends.
3.2 Shielding and grounding
For optimum electromagnetic compatibility of systems it is extremely important that the
system components, and particularly the bus cables connecting the components, are
shielded and that such shields - if possible - form an unbroken cover.
Hence, it follows that, for use in non-hazardous duty systems, the cable shield should be
grounded as often as possible.
In Ex systems an adequate equipotential bonding in the hazardous and non-hazardous
location along the entire Fieldbus installation is strongly recommended. Multiple grounding
of the shield is of advantage.
In explosion-proof systems the shielding must at least be connected at one end of the cable.
NAMUR NE 21 compliance is given, provided the above recommended cable types are used.
Core cross-section
0.8 mm
2
or
AWG 18
0.32 mm
2
or
AWG 22
0.13 mm
2
or
AWG 26
1.25 mm
2
or
AWG 16
Cable type A
AA
A B
BB
B C
CC
C D
DD
D
twisted pair,
individually
shielded
individual or
multiple twisted
pairs with overall
shield
multiple twisted
pairs, without
shielding
multiple non-
twisted cables,
without shielding
Max. length
incl. branch line
1900 m / 6200 ft 1200 m / 3900 ft 400 m / 1300 ft 200 m / 650 ft
Number of devices Cable lengths for number of devices per branch line
1 device 2 devices 3 devices 4 devices
25...32 1m/ 3.3ft 1m/ 3.3ft 1m/ 3.3ft 1m/ 3.3ft
19...24 30 m / 100 ft 1m/ 3.3ft 1m/ 3.3ft 1m/ 3.3ft
15...18 60 m / 200 ft 30 m / 100 ft 1m/ 3.3ft 1m/ 3.3ft
13...14 90 m / 300 ft 60 m / 200 ft 30 m / 100 ft 1m/ 3.3ft
1..12 120 m / 400 ft 90 m / 300 ft 60 m / 200 ft 30 m / 100 ft
INFORMATION!
The use of twisted and shielded cables is strongly recommended, otherwise EMC protection of
the signal converter cannot be assured.