User guide
OPERATION 4
57
UFC 400
www.krohne.com05/2013 - 4002813701 - AD FF UFC 400 R01 en
CLOCK_PER
CLOCK_PERCLOCK_PER
CLOCK_PER
Clock Period
Clock PeriodClock Period
Clock Period
R/W Establishes the period for periodic reset, in seconds. 0
Setting:
Positive or 0
GOOD_LIM
GOOD_LIMGOOD_LIM
GOOD_LIM
Good Limit
Good LimitGood Limit
Good Limit
R/W Sets the limit for PCT_INCL. Below this limit OUT receives the
status good.
0
Setting:
0...100%
GRANT_DENY
GRANT_DENYGRANT_DENY
GRANT_DENY
Grant Deny
Grant DenyGrant Deny
Grant Deny
R/W Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
-
Grant R/W Depending on the philosophy of the plant, the operator or a
higher level device (HLD), or a local operator's panel (LOP) in
the case of Local, may turn on an item of the Grant attribute -
Program, Tune, Alarm or Local.
Uninitialized
Setting:
Program/ Tune/ Alarm/ Local
Deny R/W The Denied attribute is provided for use by a monitoring
application in an interface device and may not be changed by
an operator.
Uninitialized
Setting:
Program denied / Tune denied / Alarm denied / Local denied
IN_1
IN_1IN_1
IN_1
Input 1
Input 1Input 1
Input 1
R/W Input 1 of the Integrator Block. -
Status Status of IN_1
Value Actual value
IN_2
IN_2IN_2
IN_2
Input 2
Input 2Input 2
Input 2
R/W Input 2 of the Integrator Block. -
Status Status of IN_2
Value Actual value
OUT_PTRIP
OUT_PTRIPOUT_PTRIP
OUT_PTRIP
Output Pre Trip
Output Pre TripOutput Pre Trip
Output Pre Trip
R/W The second discrete output. -
Status R/W Setting:
Good Non Cascade / Good Cascade / Uncertain / Bad Not
Connected / Bad
Bad Not Connected
Value R/W Setting:
0: Off / 1: On
0
Parameter
ParameterParameter
Parameter
DD name
Access Description and settings Initial Value