CONTROL_OPTS
CONTROL_OPTSCONTROL_OPTS
CONTROL_OPTS
Control Options
Control OptionsControl Options
Control Options
R/W Options which the user may select to alter the calculations
done in a control block.
No option selected
Setting:
Bypass Enable: This parameter, if true, allows BYPASS to be
set. Some control algorithms cannot provide closed loop
control if bypassed.
SP-PV Track Man: Permits the setpoint to track the process
variable when the block mode is "Man".
SP-PV Track ROut: Permits the setpoint to track the process
variable when the block mode is "ROut".
SP-PV Track LO-IMan: Permits the setpoint to track the
process variable when the block mode is "LO or IMan".
SP Track retain: Permits the setpoint to track the RCas or
Cas parameter based on the retained target mode when the
actual mode of the block is "Man, LO, Man, or Rout".
Direct acting: Defines the relationship between changes in
PV and changes to output - when direct is selected, an
increase in PV results in an increase in the output.
Track enable: This enables the external tracking function
when TRK_ENA is 1, the preset value in TRK_VAL is output if
TRK_IN_D becomes true.
Track in manual: This is used only if TRK_ENA is YES (1) -
when the block mode is Man, TRK_IN_D will be acted on only
if the TRK_OVMAN control option is set.
PV for BKCal_Out: The BKCAL_OUT value may be selected
as the working SP or the PV - normally, BKCAL_OUT is the
working SP.
Restrict SP to limits in Cas and RCas: If this option is
selected, the setpoint will be restricted to the setpoint
absolute and rate limits in Cas and Rcas modes.
No output limits in Man: Do not apply OUT_HI_LIM or
OUT_LO_LIM when target and actual modes are "Man".
DV_HI_ALM
DV_HI_ALMDV_HI_ALM
DV_HI_ALM
Deviation High
Deviation High Deviation High
Deviation High
Alarm
AlarmAlarm
Alarm
Mix The status and time stamp associated with the high deviation
alarm.
-
Unacknowledged R/W A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Alarm State R A discrete enumeration which gives an indication of whether
the alert is active and whether it has been reported.
Uninitialized
Setting:
Uninitialized
Clear - reported: Alarm not active and reported
Clear - not reported: Alarm not active and not reported
Active - reported: Alarm active and reported
Active - not reported: Alarm active and not reported
Time Stamp R The time when evaluation of the block was started and a
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
Uninitialized
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
Parameter
ParameterParameter
Parameter
DD name
Access Description and settings Initial Value