Instruction Manual

ALTOFLUX IFM x080 K-EEx and ALTOFLUX IFM x080 K / i-EEx 13
2.4 Regular IFC 090-EEx electronics unit
The field cables that enter the terminal compartment of the IFC 090-EEx signal converter unit (i.e.
power supply, current and binary outputs) are non-intrinsically safe. To connect external devices to the
signal output terminals, the wiring requirements for the type of protection of the compartment (standard:
increased safety "e", optional: flameproof "d") must be conform to the international or national standard
involved (e.g. EN 60079-14).
The terminal arrangement is shown below.
Terminal arrangement in terminal compartment
pulse and status
outputs or
control inputs
100 - 240 V AC / 48 - 63 Hz
24 V AC / DC
PE Protective ground
FE Functional ground
Passive pulse/status output
Active current output
I 150 mA
eiectronic
or electro-
mechanical
totalizer
I 150 mA
U
ext
32 V DC
24 V AC
e.g.
signal
indicator
R
i
500
Note:
The binary outputs (terminals B1, B and B2) can only be configured as passive outputs,
the current output (terminals I+ and I) can only be configured as active output.
binary
outputs
current
output