Brochure

MODEL Unit KJ-S130-AU-B KJ-S230-AU-B KJ-T130-AU-B KJ-T180-AU-B KJ-T300-AU-B
GENERATOR
Model PX-316KU1 PX-322KE1 PX-312KU3 PX-316KU3 PX-322KE3
Design Revolving field, self-excited brushless AC generator
Frequency Hz 50 50 50 50 50
Standby Output kVA 13.8 25.3 13.8 19.8 33.0
(kW) (13.8) (25.3) (11) (15.8) (26.4)
Continuous Output kVA 12.5 23.0 12.5 18.0 30.0
(kW) (12.5) (23.0) (10.0) (14.4) (24.0)
Voltage-single phase V 240 240 240 240 240
Voltage-3 phase V --- --- 415 415 415
Phase & Wire 1 Phase 4 Wire 1 Phase 4 wires 3 Phases 12 Wire 3 Phases 12 Wire 3 Phases 12 wires
Power Factory 1.0 1.0 0.8 0.8 0.8
No. of Poles 4-Pole 4-Pole 4-Pole 4-Pole 4-Pole
Insulation Class H Class H Class H Class H Class H
Voltage Regulation % 3.5 (No Load to Full Load) 3.5 (No Load to Full Load) 3.5 (No Load to Full Load) 3.5 (No Load to Full Load) 3.5 (No Load to Full Load)
Type of Coupling Direct drive Direct drive Direct drive Direct drive Direct drive
DIESEL ENGINE
Model V2203 V3300 D1703 V2203 V3300
Type Vertical, water-cooled, 4-cycle diesel engine
No. of cylinders 4 4 3 4 4
Bore x Stroke mm 87 x 92.4 98 x 110 87 x 92.4 87 x 92.4 98 x 110
Displacement mL 2197 3318 1647 2197 3318
Engine Speed rpm 1500 1500 1500 1500 1500
Continuous rated output kW (HP) 16.9 (22.6) 27.6 (37.0) 12.7 (17.0) 16.9 (22.6) 27.6 (37.0)
Lubricating oil API service class CF or higher API service class CF or higher API service class CF or higher API service class CF or higher API service class CF or higher
Oil capacity L 7.6 13.2 5.6 7.6 13.2
Coolant capacity * L 9.0 9.5 8.0 9.0 9.5
SET
Fuel Diesel fuel No.2-D (ASTM D975)
Fuel consumption at full load
L/h 5.3 7.7 4 5.3 7.7
Fuel tank capacity L 37 68 37 37 68
Continuous operating hours hrs 7.0 8.8 9.3 7.0 8.8
Battery (AH/5Hr) 95D31R (12 x 64) 130E41R (12 x 92) 95D31R (12 x 64) 95D31R (12 x 64) 130E41R (12 x 92)
Starting system Electric Electric Electric Electric Electric
L x W x H cm 148.8 x 65.0 x 97.1 173.5 x 80.5 x 104.6 139.3 x 65.0 x 97.1 148.8 x 65.0 x 97.1 173.0 x 80.5 x 104.6
Approx. Net Wt. (Wet) kg 505 630 470 505 880
Controller - Digital Control panel
DSE4520
Digital Control panel
DSE4520
Digital Control panel
DSE4520
Digital Control panel
DSE4520
Digital Control panel
DSE4520
Shutdown System - In case of abnormal : Oil pressure, water temperature
- Emergency stop button, Engine Room Door Opened, Load Center Cover removed, Low fuel, Alternator charge Fail
- Over Voltage/Frequency/Current/Power, Under voltage/Frequency
Remote start Two wire
AMPS
Current A 52.1 95.8 17.4 25.0 41.7
*Including reserve tank
DIGITAL CONTROL
PANEL
EMERGENCY STOP
BUTTON
MAIN CIRCUIT
BREAKER
Ph 1300 305 912