Housing dimensions (H x W x D) 96 x 22.5 x 110.5 mm
Housing type DIN rail housing (for DIN rail version EN 50022)
Housing material Polycarbonate
Weight approx. 100 g / 130 g (incl. connectors)
IP Code IP20
Power supply 12-24 V DC -15% / +20% (X2 and X4)
1
Max. power consumption 1.5 Watt (X4/power supply)
Operating temperature -40 °C....+55 °C
Storage temperature -40 °C....+85 °C
Humidity (at 40°C) 93% (non-condensing)
Connectors
2 x 4-pole screw-type terminal for power supply
2 x 14-pin socket connectors with spring clamp contacts (0.2 - 1.5
mm²) for IOs, pitch 3.5 mm (Wieland Item No. 27.630.4453.0)
Optical indicator 3 status LEDs (bi-color)
Number of digital output channels 16
Output type
Galvanically isolated from the system bus, individually
congurable as direct digital output with high-side or
push-pull drivers as well as a PWM output
2
Maximum current per output 500 mA (high-side mode), 100 mA (push-pull mode)
PWM frequency
Collectively selectable for all outputs: 40 Hz, 80 Hz, 160 Hz,
200 Hz, 400 Hz
2
Alarm
Thermal shutdown or short circuit of outputs (individually for each
output)
Dual watchdog function
In the event of communication failure with the controller (after 50
ms) or internal communication with the CPU (after 9 ms, hardware-
controlled), the outputs are reseted to zero
Output protection
According to EN 61131-2 (IEC 61000-4-4, -5, -6, and -2) against short
circuit, overload, external voltage, negative voltages, burst,
surge, ESD, RFI
1
Two independent supply voltage sources must be available for galvanic isolation of the outputs.
Technical Data
Version: EN 1.0
page 1/2Errors excepted and possible alterations without prior notice.
KUNBUS GmbH, Heerweg 15C, 73770 Denkendorf, Germany | Tel: +49 (0)711 300 20 678 | Fax: +49 (0)711 300 20 677 | Email: info@kunbus.com | Web: www.kunbus.com
2
The PWM pulse width is stored as a value from 0 to 100 in the process image in 1 byte. The maximum resolution of the conversion of this value in % by the
module depends on the PWM frequency: 40 Hz / 1%, 80 Hz / 2%, 160 Hz / 4%, 200 Hz / 5%, 400 Hz / 10%.