RevPi Connect
Article No.: 100274
Housing dimensions (H x W x D) 96 x 45 x 110.5 mm
Housing type DIN rail housing (for DIN rail version EN 50022)
Housing material Polycarbonate
Weight approx. 197 g / 224 g (incl. connectors)
IP Code IP20
Power supply 12-24 V DC -15%-/ +20%
Max. power consumption 20 Watt (incl. 1 A total USB output current)
1
Operating temperature -40 °C....+55 °C
2
Storage temperature -40 °C....+85 °C
Humidity (at 40°C) 93% (non-condensing)
Interfaces
2 x USB A (Total current draw from both sockets max. 1 A)
3
2 x RJ45 10/100 Ethernet (using separate MAC addresses)
1 x RS485 screw-type terminal (not galvanically isolated)
1 x Micro-USB (solely for image transfer to eMMC)
1 x Micro HDMI
1 x PiBridge system bus
1 x ConBridge system bus
Connectors
1 x 4-pole screw-type terminal for relay contact and signal input
1 x 8-pole spring clamp connector for power supply
Processor Broadcom BCM2837 quad-core ARM Cortex A53 (ARMv8)
Clock rate 1.2 GHz
2
Processor cooling Passive with heat sink
RAM 1 GByte
Flash memory 4 GByte
3
1 A USB output current (total of both USB outputs) is only available for input voltages >11 V. The bridging time of at least 10 ms required by EN 61131-2 is only guaranteed with a 20.4 to 28.8 V
power supply. With a 12 V power supply, this time is signicantly reduced, especially when power is drawn from the USB ports.
1
The average power consumption without USB load varies greatly and depends on the use of the interfaces, the GPU and the CPU. It is usually well below 4 watts without HDMI.
Technical Data
2
There should be no cutbacks of power at ambient temperatures below 20°C. At 25°C ambient temperature 3 cores may run with full clock speed while with 4 cores the clock frequency
is lowered from 1.2 to 1.1 GHz after 10 to 20 minutes of full stress. At 40°C ambient temperature 4 cores under full stress will still work with 1 GHz while stressing just 1 core results in no
down clocking. At 50°C ambient temperature 4 fully stressed cores are running at average 0.7 GHz, having short down clockings to 0.6 GHz and short up clockings to 0.9 GHz. 1 core under full
stress does result in no down clocking. At 65°C ambient temperature and either 4 or 1 core under full stress results in an “emergency mode” with just 0.4 GHz, after longer periods even 0.3 GHz.
Version: EN 1.0
page 1/2Errors excepted and possible alterations without prior notice.
KUNBUS GmbH, Heerweg 15C, 73770 Denkendorf, Germany | Tel: +49 (0)711 300 20 678 | Fax: +49 (0)711 300 20 677 | Email: info@kunbus.com | Web: www.kunbus.com