Spec Sheet

SPECIFICATIONS KPAC2421-2
COOLING CAPACITY
BTU/hr @ 95F at 60% RH 22,900 (2-Ton)
COMPRESSOR DATA
Compressor Type Hermetic Rotary
Operating Temperatures 70-105 F 50%RH
Refrigerant 410A
FAN DATA
Evaporator
Fan Type (Centrifugal) Direct Drive
Air Flow (CFM) 810/1Speed
Supply Air Device 2 - 6" Dia. x 18" Air Chute
Supply Air Duct max. length 25'
Condenser
Fan Type (Centrifugal) Direct Drive
Air Flow (CFM) 1100
Condenser Duct Specs (optional) 1 - 14" Dia. x 8' Length
Condenser Duct Max. Length 25'
ELECTRICAL DATA
Power Supply (Volts) 208/230 Single Phase
Current Consumption (Amps) 10.6/9.6
Power Consumption (kW) 2.0
Maximum Circuit Breaker (Amps) 20
Recommended Breaker Size 20
Minimum Circuit Ampacity (Amps) 14.3
Min./Max. Voltage 195-225/210-250
Power Cord Gauge/Length 12/7'
Plug Configuration NEMA 6-20
DIMENSIONAL DATA
Width x Depth x Height (Inches) 20.325" x 26" x 44"
Weight (Lbs.) 206
Shipping Weight (Lbs.) 266
Ceiling Kit Weight (Lbs.) 24
Shipping Weight w/ Ceiling Kit 290
SAFETY DEVICE DATA
Compressor Overload Internal
Fan Motor Overload Automatic Internal
Evaporator Freeze Protection Freeze Stat
High Pressure Switch Manual
Compressor Short Cycle Yes
Automatic Restart Yes
Thermostat Type Microprocessor/Digital
Condensate Pump Overflow Optional
Condensate Tank Overflow Yes
1-800-KWIKOOL
www.kwikool.com