Owner manual

KEW3128 49
KEW3128 6. Measurement
6. 4 PI Measurement (Polarization Index)
6.4.1Polarization Index
  PI : Polarization Index
   This is a test to check a temporal increase of leakage currents flowing on
insulations. To determine a Polarization Index, first, measure insulation
resistance at 1 min intervals for 10 min. Then, divide the final value by
the initial reading and calculate a ratio. PI is dependent on the shape of
insulations
and influenced by moisture absorption, therefore, a check of PI
is important to diagnosis the insulation of cables.
Polarization index =
TIME 2
Insulation resistance value 3 or 10 min
after starting measurement
TIME 1
Insulation resistance value 30 sec or 1 min
after starting measurement
PI 4.0 or more
4.0 2.0 2.0 1.0
1.0 or less
Criteria Best Good Warning Bad
6.4.2 How to measure PI
  1. Select the PIPolarization Index on the Mode Selection Screen.
Refer to Basic Operation (=>P.21) and operate the Screen.