Manual

̶
14
̶
Forthisexamplethemaxpermissiblevalueis1667Ω(RCD=30mA
and contactvoltagelimit of 50 V).The instruments reads 12.74Ω,
thus the condition RA ≤ 50/Ia is respected. However, considering
that theRCD is essential for protection, itmustbe tested (Please
refertoRCDTESTSsection).
TN System
For TN systems the earth fault loop impedance is the sum of the
following impedances.
●Impedanceofthepowertransformersecondarywinding.
●Impedanceofthephaseconductorfromthepowertransformerto
the location of the fault.
●Impedance of the protective conductor from the fault location to
the power transformer.
The figure below shows (dotted line) the Fault loop impedance for
TN systems.
Fig.7-3
According to the International Standard IEC 60364, for TN
system the characteristics of the protective device and the circuit
impedance shall fulfill the following requirement:
Zs x Ia ≤ Uo Where:
Zs is the Fault loop impedance in ohm.
Uo is the nominal voltage between phase to earth (typically 230V
ACforbothsinglephaseandthreephasecircuits).
Ia is the current causing the automatic disconnection of the
protective device within The maximum disconnecting times required
byIEC60364-41thatare: