Manual
̶
14
̶
Forthisexamplethemaxpermissiblevalueis1667Ω(RCD=30mA
and contactvoltagelimit of 50 V).The instruments reads 12.74Ω,
thus the condition RA ≤ 50/Ia is respected. However, considering
that theRCD is essential for protection, itmustbe tested (Please
refertoRCDTESTSsection).
TN System
For TN systems the earth fault loop impedance is the sum of the
following impedances.
●Impedanceofthepowertransformersecondarywinding.
●Impedanceofthephaseconductorfromthepowertransformerto
the location of the fault.
●Impedance of the protective conductor from the fault location to
the power transformer.
The figure below shows (dotted line) the Fault loop impedance for
TN systems.
Fig.7-3
According to the International Standard IEC 60364, for TN
system the characteristics of the protective device and the circuit
impedance shall fulfill the following requirement:
Zs x Ia ≤ Uo Where:
Zs is the Fault loop impedance in ohm.
Uo is the nominal voltage between phase to earth (typically 230V
ACforbothsinglephaseandthreephasecircuits).
Ia is the current causing the automatic disconnection of the
protective device within The maximum disconnecting times required
byIEC60364-41thatare: