Owner's manual
̶
3
̶
2. Features
This instrument is a digital clamp-on earth resistance tester, and it is used in multi-
earthed systems. Can measure the earth resistance by simply clamping around the
earthed wires.
This instrument also equips AC current function to measure current up to
30
A
same as our traditional leakage clamp meters.
A single earthing cannot be measured. (only for multiple-earthing system)
Wide measuring range (Auto-ranging)
Earth/ground resistance Max.
1200
Ω
Min. resolution
0
.
01
Ω
AC current Max.
30
A Min. resolution
0
.
1
mA
Noise check function
A function to detect current, which effects on an earth resistance measurement
and display the NOISE symbol on the LCD.
True RMS
Accurate true RMS readings of AC current with distorted waveform.
Auto power-off function
A function to prevent the
instrument from being left turned on and conserve
battery power.
Data hold function
A function to freeze the measured value on the display.
Buzzer function
A function to give audible warning to the user when the measurement result is
10
Ω
or less.
Backlight function
A function to facilitate working at dimly lit areas.
Memory function
A function to save and display the measurement r
esult.
Designed to following safety standard.
IEC
61010
-
1
(CAT.IV
300
V Pollution degree
2
), IEC
61010
-
2
-
032
This instrument is protected by double or reinforced insulation
.
●
Bluetooth Communication Function (KEW
4202
only)
Remote checking of measurements is possible without accessing KEW
4202
unit by connecting KEW
4202
and Android devices via Bluetooth.