Owner's manual

̶
3
̶
 2. Features
This instrument is a digital clamp-on earth resistance tester, and it is used in multi-
earthed systems. Can measure the earth resistance by simply clamping around the
earthed wires.
This instrument also equips AC current function to measure current up to
30
A
same as our traditional leakage clamp meters.
A single earthing cannot be measured. (only for multiple-earthing system)
󱛠
Wide measuring range (Auto-ranging)
Earth/ground resistance Max.
1200
Ω
Min. resolution
0
.
01
Ω
AC current Max.
30
A Min. resolution
0
.
1
mA
󱛠
Noise check function
A function to detect current, which effects on an earth resistance measurement
and display the NOISE symbol on the LCD.
󱛠
True RMS
Accurate true RMS readings of AC current with distorted waveform.
󱛠
Auto power-off function
A function to prevent the
instrument from being left turned on and conserve
battery power.
󱛠
Data hold function
A function to freeze the measured value on the display.
󱛠
Buzzer function
A function to give audible warning to the user when the measurement result is
10
Ω
or less.
󱛠
Backlight function
A function to facilitate working at dimly lit areas.
󱛠
Memory function
A function to save and display the measurement r
esult.
󱛠
Designed to following safety standard.
IEC
61010
-
1
(CAT.IV
300
V Pollution degree
2
), IEC
61010
-
2
-
032
󱛠
This instrument is protected by double or reinforced insulation
.
Bluetooth Communication Function (KEW
4202
only)
Remote checking of measurements is possible without accessing KEW
4202
unit by connecting KEW
4202
and Android devices via Bluetooth.