LED indication of correct The P-E and P-N LEDs illuminate when
the wiring of the circuit under test is
correct. The reverse LED is lit when P
and N are reversed.
Auto data hold The LCD reading is automatically frozen for
3 seconds after measurement.
Display The liquid crystal display has 3 1/2 digits
with a decimal point and units of
measurement (ms, mA).
Over voltage Halts measurement to prevent damages to
the body when voltage between phase and
earth is approx. 260V or more. "VL-PE Hi"
is shown on the display.
Symbols used on the Equipment protected throughout by
DOUBLE INSULATION or REINFORCED
INSULATION.
Caution(refer to accompanying instruction
manual)
polarity
instrument
Function Operating error of trip current
×1/2
×1
×5
AUTO RAMP
-10∼0%
0∼+10%
-10%∼+10%
● Operating error of trip current (IEC/EN 61557-6)
The influencing variations used for calculating the operating error are
denoted as follows:
Temperature:0℃ and 40℃
Earth electrode resistance:max 50Ω(max 20Ω at ×5 500mA only)
System voltage:230V+10%-15%