7. Preparation
7-1 Connection of Test Leads
Connect the test lead properly.
Connect the test lead M7128; red cord to the load of the Connector
block and black cord to the power supply.
When using the test lead with Alligator clip, connect the test lead
M7128 (red) to the load of Connector block and M7129 to the power.
7-2 Setting of Measurement Range
Turn the Function Switch and power on the instrument, then select any
appropriate Ranges.
Range construction: There are 4 Ranges on this instrument.
x 5 For trip time measurement :
Apply a current 5 times bigger than IΔn to measure
RCD trip time.
x 1 For trip time measurement :
Apply IΔn to measure RCD trip time.
x 1/2 For the test - rated residual non-operating current :
Apply a half of IΔn to confirm the RCD under test
doesn’t trip.
AUTO RAMP For trip out current measurement :
Vary a testing current in the range of 40% ~ 110% of
IΔn to measure the trip out current on the RCD.
WARNING
Do not power on the instrument with it being connected to the live
circuit.