Owner's manual

̶
13
̶
5.1 Principles of Measurement
5.1-1 Measurement of Fault Loop Impedance and Prospective Fault
Current
If an electrical installation is protected by over- current protective devices
including circuit breakers or fuses, the earth fault loop impedance should be
measured.
In the event of a fault the earth fault loop impedance should be low enough
(and the prospective fault current high enough)to allow automatic
disconnection of the electrical supply by the circuit protection device within a
prescribed time interval.
Every circuit must be tested to ensure that the earth fault loop impedance
value does not exceed that specified or appropriate for the over- current
protective device installed in the circuit.
For a TT system the earth fault loop impedance is the sum of the following
impedances;
Impedance of the power transformer secondary winding.
Impedance of the phase conductor resistance from the power transformer
to the location of the fault.
The impedance of the protective conductor from the fault location to the
local earth system.
Resistance of the local earth system (R).
Resistance of the power transformer earth system (Ro).
 
5. LOOP IMPEDANCE / PSC TESTS
Fig.9