5.1 Import ant preliminary checks
DANGER
Do not make measu remen ts on a circui t in w hich ele ctri cal p oten tial exce eds AC 600 V.
Connect the Pow er cord to a socket outlet. Never connect it to the socket outlet of AC240V or more.
The Clamp sensor, Voltage test leads and Power cord are to be connected to the instrument first.
The Voltage test leads or Clamp sensors should not be connected to the input terminals of the instrument
if not required for measurement.
The instrument should always be connected on the downstream side of a circuit breaker, which is safer
than the upstream side .
Do not open-circuit the secondary side of a supplementary CT while it is energized because of the high
voltage generated at the secondary side terminals.
Be careful to avoid short-circuiting the power line with the un-insulated part of the voltage test probes
during the setting up of the instrument. Transformer jaw tips are designed in su ch a way to avoid
short-circuiting . If the ci rcuit un der te st ha s exposed condu cti ve pa rts, ex tra ca re sho uld be taken to
minimize the possibility of shorting.
WARNING
To avoid possibl e ele ctric shock and shor t-circuit, al w ays turn off the line under test when setting up the
instru me nt.
Do not touch the un-insulated tip of Voltage test probes. The use of safety insulted gloves is recommended.
Direction for correct measurements
Proper setting of wiring configuration should be made.
Ensure that the arrow mark on the cl amp sen sor poin ts towards to load side.
* Reverse clamping switches the symbols (+/-) for active power [P].
Arrow mark: Points
towards load side.
Load
Source