User Manual
11.2.2 Power quality – Measuring Procedure (Swell/ Dip/ Int measurement) KEW6310
11.5 KEW6310
201 date pts
recorded
S t art of Swell
End of Swell
100%
(reference
voltage)
110%
(Swell)
109%
(Swell110%- Hysteresis1%)
100 100
Duration
Trigger
Trigger
RMS(max)
data
p
ts
201 date pts
recorded
100 100
data
p
ts
Timing of data recording
<Recording at event occurrence>
① <Swell>
Star t of Dip
End of Dip
100%
(Reference
voltage)
90%
(Dip
91%
(Dip90%+Hysteresis1%)
Duration
Trigger
Trigger
RMS(min)
②
<Dip>
201 date pts
recorded
100
100
data
p
ts
201 date pts
recorded
100
100
data
p
ts
Star t of Int
End of Int
100%
(Reference
voltage)
10%
( Int )
11%
(Int10%+Hysteresis1%)
Duration
Trigger
Trigger
RMS(min)
③ <Int>
201 date pts
recorded
100
100
data
p
ts
201 date pts
recorded
100
100
data
p
ts