● Safety warnings
This instrument has been designed, manufactured and tested according to IEC 61010: Safety requirements
for Electronic Measuring apparatus, and delivered in the best condition after passing quality control tests.
This instruction manual contains warnings and safety rules which have to be observ ed by the user
to ensure safe operation of the instrument a nd to maintain it in safe condition. Therefo re, rea d through
these operating instructions before us ing the instrument.
WARNING
● Read through and understand the instructions contained in this manual before using the instrument.
● Keep the manua l at ha nd to enable qui ck referen ce w hene ver ne cessa ry.
● The instrument is to be used only in its intended applications.
● Understand and follow all the safety instructions contained in the manual.
● Read the enclo sed Qu ick manua l after reading th is instru ction manua l.
● As to the Clamp sensor use, refer to the instruction manual supplied with the sensor.
It is essential that the above instructions are adhered to. Failure to follow the above instructions may cause
injury, instrument damage an d/ or dama ge to equip ment un der test.
The symbol indicated on the instrument, means that the user must refer to the related part s in the manual
for safe operation of the instrument. It is essential to read the instructions wherever the symbol appears in
the manual .
DANGER
is reserved for conditions and actions that are likely to cause
serious or fat al inju ry.
WARNIN G
:
:
is reserved for conditions and actions that can cause serious or
fatal injury.
CAUTION
:
is reserved for conditions and actions that can cause injury or
instrument damage.
This instrument meets CAT. III 600V. To ensure safe operation of measuring instruments, IEC 61010 establishes
safety standards for various electrical environments, categorized as CAT.I to CAT.IV, and called measurement
categories. Hi ghe r-num bere d catego rie s co rrespond to el e ctri cal en vi ron men ts w ith gr eater mo ment ary energy ,
so a measuring instrument designed for CAT.III environments can endure greater momentary energy than one
designed for CAT.II.
CAT.I: Secondary electrical circuits connected to an AC electrical outlet through a transformer or similar device.
CAT.II: Primary electrical circuits of equipment connected to an AC electrical outlet by a power cord.
CAT.III: Primary electrical circuits of the equipment connected directly to the distribution panel, and feeders from
the distribution panel to ou tle ts.
CAT.IV: The circuit from the service drop to the service entrance, and to the power meter and primary overcurrent