User Manual

KEW6310 4.2.2 Measurement Setting (QUALITY-Swell, Dip, INT Measurement)
4.41 KEW6310
Setting for dip
5~ 100% (can be se t by 1%)
* Default value (or after system reset) : 90%
1 Press the Cursor Keys and select [Dip], and then press the ENTE R Key.
2 Press the Cursor Keys and alter values, and then press the ENTER Key.
Lower limit varies dep en ding on the selected refe rence vo lt ag e.
70 ~ 150V : percentage to obtain values of 7.5 or more
151 ~ 300V : percentage to obtain values of 15.0 or more
301 ~ 600V : percentage to obtain values of 30.0 or more
601 ~ 1000V : percentage to obtain values of 50.0 or more
Box with ▲▼ mark appears
at the rightmost digit.
Selected dip is displayed.