User Manual

4.2.2 Measurement Setting (QUALITY-Inrush Current Measurement) KEW6310
4.51 KEW6310
Setting for Inrush Current Measurement
For the details of Inrush Current, refer to “1 1 .4 Inrush Current Measurement” in this manual.
Setting Items
Interval
*1
set interval time
Clamp sensor : refer to Basic setting
A Range : refer to Basic setting
Reference current : select a Current Range of reference
Filter : refer to Basic setting
Threshold value : set in percentage against reference current
Hysteresis : set in percentage against reference current
T rigger Point : set a number of data save point prior to / following an event of trigger
* Selectable ra nge fo r reference current (A/mA) is automatically displayed af te r sele cti ng a Curren t
Range for 1ch at Basic setting.*1 Flicker measurement function is only available with ver.2.00 or later.
Setting for interval
* Default value (or after system reset) : 30 min
* Setting procedure is same to that for interval Setting for W/ Wh/ DEMAND.Refer to the procedure described in
the preceding pages.
Setting for referent current
Current Range Selectable range Resolution
100mA 10 ~ 100mA 0.1m A
500mA 50 ~ 500mA 0.1m A
1A 0.1 ~ 1A 0.001A
5A 0.5 ~ 5A 0.001A
10A 1 ~ 10A 0.01A
20A 2 ~ 20A 0.01A
50A 5 ~ 50A 0.01A
100A 10 ~ 100 A 0.1A
200A 20 ~ 200 A 0.1A
500A 50 ~ 500 A 0.1A
1000A 100 ~ 1000A 1A
3000A 300 ~ 3000A 1A
* When “AUTO” is selected as a Current Range for A1, the max Range of Clamp
sensor is set automatically.
* Selectable ra nge i s with in 10 to 100% o f Cu rren t Range .