12.2 Troubleshooting Table
This table includes a listing of the fault codes that may be displayed. Some of these can be corrected by
changing a parameter, while other conditions are more complicated, and will require a service technician.
The rst column lists the code number that will appear at the beginning of the Lockout or Hold message in
the orange bar at the bottom of the screen. The second column lists the text as it will appear on the Touch
Screen. The third column shows whether the condition will cause a Hold, or Lockout, or both. The fourth
column lists some suggestions for corrective action.
Code Description Lockout
or Hold
Procedure
1 Uncongured safety data L 1. New device, complete device conguration and
safety verication.
2. If fault repeats, replace module
2 Waiting for safety
data verication
L 1. Device in Conguration mode and safety
parameters need verication and a device
needs reset to complete verication.
2. Conguration ended without verication, re
enter conguration, verify safety
parameters and reset device to complete
verication.
3. If fault repeats, replace module.
3 Internal fault:
Hardware fault
H Internal fault
1. Reset module
2. If fault repeats, replace module.
4 Internal fault:
Safety Relay key feedback error
H Internal fault
1. Reset module
2. If fault repeats, replace module.
5 Internal fault:
Unstable power (DC DC) output
H Internal fault
1. Reset module
2. If fault repeats, replace module.
6 Internal fault:
Invalid processor clock
H Internal fault
1. Reset module
2. If fault repeats, replace module.
7 Internal fault:
Safety relay drive error
H Internal fault
1. Reset module
2. If fault repeats, replace module.
8 Internal fault:
Zero crossing not detected
H Internal fault
1. Reset module
2. If fault repeats, replace module.
9 Internal fault:
Flame bias out of range
H Internal fault
1. Reset module
2. If fault repeats, replace module.
10 Internal fault:
Invalid burner control state
L Internal fault
1. Reset module
2. If fault repeats, replace module.