Installation, Operation and Maintenance Instructions User guide

MagnaTherm Boilers and Water Heaters
Page 79
Code Description Lockout
or Hold
Procedure
187 Invalid DHW (Domestic Hot Water)
high limit enable setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
188 Invalid DHW (Domestic Hot Water)
high limit response setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
189 Invalid ame sensor type setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
192 Invalid igniter on during setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
193 Invalid ignite failure delay setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
194 Invalid ignite failure response setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.\
195 Invalid ignite failure retries setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
196 Invalid ignition source setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
197 Invalid interlock open response setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
198 Invalid interlock start check setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
199 Invalid LCI (Limit Control Input) enable
setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.