Installation, Operation and Maintenance Instructions User guide
MagnaTherm Boilers and Water Heaters
Page 81
Code Description Lockout
or Hold
Procedure
214 Invalid Prepurge time setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
215 Invalid Purge rate proving setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
216 Invalid Run ame failure response
setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
217 Invalid Run stabilization time setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
218 Invalid Stack limit enable setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
219 Invalid Stack limit response setting L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
220 Uncongured Delta T limit setpoint
setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
221 Uncongured DHW (Domestic Hot
Water) high limit setpoint setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
222 Uncongured Outlet high limit setpoint
setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
223 Uncongured Stack limit setpoint
setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
224 Invalid DHW (Domestic Hot Water)
demand source setting
L 1. Return to Conguration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.