Install and Operating Manual User guide

LAARS Heating Systems
Page 28
SECTION 9.
Modes of Operation
The Mascot II control allows the boiler to operate
in many different modes of operation. The mode must be
selected based upon the requirements of the installation.
The following sections describe the basic operation of
the Mascot II in each of the different modes. Familiarize
yourself with each mode and how the operation of the
boiler varies, depending upon the installation and inputs
the control is monitoring.
9.1 Hydronic Heating Demand
When using the Mascot II for hydronic heating a
call for heat must be supplied to the "T-T or Interlock"
terminal. Once the call is supplied the control starts the
boiler and system pumps, shifts the 3-way valve position
and begins the ignition process. The ignition process
consists of a prepurge, trial for ignition, and run period.
The prepurge period starts on a call for heat once the fan
RPM reaches a preset level. The trial for ignition period
follows once the start-up RPM of the fan is reached. The
trial for ignition period lasts 4 seconds during which the
direct spark ignition system and gas valve are energized.
At the end of the trial for ignition period the ame signal
is compared with the preset ame threshold value. If
the ame signal is higher than the ame threshold the
Mascot II enters "run". If the ame signal is below the
threshold the Mascot II returns to prepurge and starts the
ignition process over. In "run" the Mascot II monitors
the ame signal, call for heat, safeties, and water
temperatures and modulates as needed between 100%
and 20% of rate to satisfy the call for heat.
9.2 Hydronic Heating with Outdoor Reset
Outdoor reset varies the control point setpoint
based on the actual outdoor temperature. The reset
function works as shown in Figure 24. When the
outdoor air temperature reaches the "high outdoor
temperature setpoint (HOD), the control point setting is
adjusted to the low boiler temperature setpoint (LBT).
When the outdoor air temperature reaches the low
outdoor temperature setpoint (LOD), the control setpoint
is adjusted to the CH/Outlet water setpoint temperature.
HOD, LOD and LBT can be adjusted by accessing
SETUP mode. CH setpoint is adjustable from the USER
menu structure.
9.3 Hydronic Heating Using External
Modulation Control
When using the Mascot II for hydronic heating
with external modulation control a call for heat must
be supplied to the "T-T" terminal. Once the call is
supplied the control starts the boiler and system pumps
and begins the ignition process. In "run" the Mascot II
monitors the ame signal, call for heat, safeties, and
NAME FUNCTION DEFAULT
VALUE
CH on Burner demand begins when the 5°F
differential outlet water temperature reaches
"Outlet water temperature setpoint"
minus "CH on differential"
CH off Burner demand ends when the 5°F
differential outlet water temperature reaches
"Outlet water temperature setpoint"
plus "CH off differential"
DHW on Burner demand begins when the 2°F
differential outlet water temperature reaches
"Outlet water temperature setpoint"
minus "DHW on differential"
DHW off Burner demand ends when the 7°F
differential outlet water temperature reaches
"Outlet water temperature setpoint"
plus "DHW off differential"
Pump Operates the pump for the overrun 1
overrun time after the burner demand minute
has ended
High Locks the boiler out when the high 200°F
limit limit temperature is reached
(requires manual reset)
Flame Flame signals lower than the ame 0.8Vdc
threshold threshold interrupt burner operation
Table 12. Default Control Settings.
on when the water temperature reaches 115°F. Set the
hysteresis values to match the boiler to the system
operating characteristics. Setting this value correctly
will help reduce the chance of short cycling.
8.8.5 Lead Lag Base Load Setting
The lead lag system uses a base load setting that is
set through the "setup" menu called "bL". The base load
setting identies the ring rate that the operating boiler
must achieve before the next boiler in the system is
allowed to operate. The default setting is 50% to avoid
short cycling and operating the boilers at higher, less
efcient, ring rates.