5.1.1 Changing Single Circuit to Two
Circuits
Sizes 500 to 1500 will be shipped from the factory
for a single 120-volt power supply. To use a separate
circuit for the pump:
1. Ensure power is disabled to the unit.
2. Remove the three jumper wires that connect the
L2, N2 and GROUND wires on terminal block 1
to the main distribution terminal block. These
wires will be black/white, white and green
respectively.
5.2 Field Wiring
Main Power: The main eld wiring connection
points are located inside the line voltage connection/
WARNING
The appliance must be electrically grounded in
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
All electrical connections are made in the eld
wiring terminal strip, which is located at the right side of
the appliance.
NOTE:
5.1 Main Power
All Mighty Therm2 non-pump-mounted heaters
require a single 120-volt fused supply. See Figure 15 for
over current protection ratings.
Pump-mounted Mighty Therm2 models 500 to
1500 use a single 120-volt fused supply. The installer
can change these units to use a separate circuit for the
pump, if desired. Instructions to make this change are
found in Section 5.1.1.
Pump-mounted Mighty Therm2 models 1750
and 2000 require two 120-volt fused supplies. See Figure
15 for over current protection ratings.
Figure 16. Mighty Therm2 (500–750) Wiring Diagram.Figure 15. Field Wiring.
500 15 20 15 15
1250 25 30 15 15
1500 25 30 15 15