Special attention should be paid to clearances
between the front of the boiler and the closet door
when it is closed.
Consult the American National Standard Z21.13 for
more information concerning closet installations. In
Canada, refer to the latest edition of CSA-B149.1.
Figure 2JVS. Closet Installation
Dimensions in inches cm.
6 15
6 15
6 15
4*
10
*6" for models JV160 to JV225.
width and depth of the heater by at least 12 inches
(305mm) in all directions. The masonry must be laid
with ends unsealed, and joints matched to provide
free circulation of air from side to side through the
masonry (see Figure 1). If the boiler is installed in a
carpeted alcove, the entire oor of the alcove must be
covered by a noncombustible platform.
2E. Clearance / Closet Installations
All Mini-Therm JV's can be installed in a closet as
long as the minimum clearances are observed.
See Table 2JVH and Figure 2JVH for
clearances required for the Mini-Therm JVH.
See Table 2JVS and Figure 2JVS for
clearances required for the Mini-Therm JVS
Figure 2JVH. Closet Installation.
TOP
VIEW
SIDE
VIEW
2
(51)
A
2
(51)
5
(127)
6
(152)
6
(152)
MIN
Dimensions in
inches (mm).
Air
Openings
B
Note: Clearances listed are manufacturer’s tested values. These are given as minimum values. Where local and national
codes apply, and values are different than those listed use the greater value to ensure safe operation.
Minimum Boiler Clearances from Combustible Surfaces.
Dégagements Minimaux à Assurer Entre Ics Parois de L’appareil et leo Constructions Combustibles
Boiler Sizes 50 - 225
Clearances in cm
Left side 2 5
Right side 5 15
Rear 2 5
Front 4 10
Flue (using B-vent) 6 15
Top 23 58
Boiler Sizes 50 - 125 160 - 225
Clearances in cm in cm
Left side 6 15 6 15
Right side 6 15 6 15
Rear 6 15 6 15
Front 4 10 4 10
Flue 6 15 6 15
Top 23 58 36 91
Table 2JVS Minimum Boiler ClearancesTable 2JVH Minimum Boiler Clearances