Install Instructions

LAARS Heating Systems
Page 20
CAUTION
Condensate is mildly acidic (pH=5), and may harm some ๎ƒ€oor drains and/or pipes, particularly those that are
metal. Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand
the acidity, or neutralize the condensate before disposal. Damage caused by failure to install a neutralizer kit
or to adequately treat condensate will not be the manufacturerโ€™s responsibility.
Contact Laars to order Kit# A2123601
__________________________________________________________________________________________
Figure 13. DHW Connections with Anti-Scald Valve
and Flow Restrictor.
6.7 Condensate Drain
A condensate drain trap is built into the Mascot LX.
Connect a 3/4โ€ PVC pipe between the drain connection
and a condensate neutralizer before entering drainage
system.
The condensate drain and included trap must be
installed. When a condensate pump is not used, the
tubing must continuously slope downward toward the
drain with no spiraling.
Consult local codes for the disposal method.