User guide
Chapter 2: Prerequisites 
Product Service 1-800-522-7658 
4 
Original instructions 
Exhaust Requirements 
If you intend to connect the Procedure Station to the optional Ventus
TM
Canopy Connection Kit, first examine the location to ensure that it 
accommodates the cabinet’s exhaust duct. The area directly above the 
cabinet’s exhaust port should be clear of structural elements, water and utility 
lines, or other fixed obstructions. There should be enough clearance to 
accommodate a 10-inch diameter duct. Avoid cabinet locations that require 
an elbow directly above the cabinet’s exhaust connection or an excessive 
number of elbows in the exhaust system. For further information about the 
cabinet’s exhaust system requirements, please refer to Chapter 3: Getting 
Started. 
Electrical Requirements 
The procedure station models have the following electrical requirements: 
Model #  Requirements 
31x4xxx0x  115 VAC, 60 Hz, 12 Amps 
31x4xxx1x  100 VAC, 50/60 Hz, 12 Amps 
31x4xxx-20, 30, 40, 50, 60, 70  230 VAC, 50/60 Hz, 6 Amps 
31x6xxx0x  115 VAC, 60 Hz, 16 Amps 
31x6xxx1x  100 VAC, 50/60 Hz, 16 Amps 
31x6xxx-20, 30, 40, 50, 60, 70  230 VAC, 50/60 Hz, 8 Amps 
Note: A dedicated outlet with an appropriate circuit breaker should be 
located as close as possible to the right rear side of the cabinet, at a 
height even with, or higher than, the top of the bench or stand. Consult 
your local electrical codes for properly rated circuit breakers. For safe 
operation the dedicated outlet must provide the protective earthing 
ground connection to the cabinet. 
Note: On 100 and 115 VAC models, both electrical outlets are protected by a 
ground fault interrupter circuit (GFIC). Labconco does not recommend 
plugging the procedure station into a GFIC outlet. 
  Electrical outlets in the cabinet are restricted to 5 amps 
maximum current. 
Prises électriques dans l'armoire sont limitées à 5 courant 
maximum ampères. 
Table 2-1 










